11. Febrero 2009
Gas Dehumidification incl. Condensate Drainage in France
Technical data:
- Gas volume flow: 700 Nm³/h
- Gas inlet temperature: 35°C
- Cooling to approx. 5°C
- Relative humidity at outlet approx. 30%
Designed as FriCon for outdoor installation
In comparison with conventional systems, the cooling capacity is ensured by both an air-cooled liquid chiller and the process gas itself. This reduces the cooling demand, so cutting operating costs by 14%!

Special features:
One specification made by the customer was explosion-proofing of the entire plant. This is why the cold water set and gas cooling unit are spaced 3 m apart. The condensate produced is discharged to a collection tank. Explosion protection is provided for the condensate pump and 4-point level switch (pump on/off, high/low water alarm).
The provisions of French law were satisfied by CE marking for the entire system (subassembly).